VFDs - Technical Details

Enhanced Function

Time- Delay relay Simple logic programming for the multi-functional output terminals and the digital input terminals. The logic results can be equivalent to the digital input terminal function, and can be output through the multi-functional output terminals

Internal Timer

Two internal timers to collect timing input signals and to output timing signals. The two timers can be used separately or together

Internal math operator module

One internal 4-way math module for elementary arithmetic operations, numerical magnitude judgment and integral operation

 

Communication

E100 The control panel has a RS485 communication interface which supports standard MODBUS-RTU protocol
E102/ E180/ EM60

The control panel does not have a RS485 communication interface, and an external 485 communication expansion card shall be connected. Support standard MODBUS-RTU protocol. The E180 series also support standard PROFIBUS-DP protocol (through an external E180-DP expansion card)

 

Coder

E100 The coder can be connected directly through the DI5 and DI6 terminals on the control panel, and simple closed-loop control is available through PID control. Such connection is used in undemanding situations
EM60 The control panel does not have any interface for the coder, and a one-way high-speed pulser can be extended (through DI6)
E102 The control panel only has one coder interface (DI6)
E180 The control panel does not have any coder interface, and an external coder expansion card is necessary. The inverter supports ABZ incremental coder, UVW incremental coder and resolver. Such connection enables high-performance VC, and can be used in situations with demanding control precision requirements

 

Motor

E100/E102 Only for asynchronous motors
E180 For asynchronous motors and synchronous motors

 

Display

Operation Information Given frequency, output frequency, output voltage, busbar voltage, input signal, feedback value, module temperature, and synchronous speed of the motor. At most 32 parameters can be displayed in cycle through the “>>” key

 

Protection

Inverter Protection Over-current, over-voltage, module fault protection, under-voltage, overheat, overload, external fault protection, EEPROM fault protection, ground protection, and default phase
Inverter Alarm Locked-rotor protection, overload alarm
Instantaneous Power Down Less than 15ms: continuous operation More than 15ms: automatic restart

 

Environment

Ambient Temperature -10 C to 40 C
Storage Temperature -10 C to 40 C
Ambient Humidity Max. 90% RH (No condensation)
Altitude/Vibration
Below 1000m; below 0.6g
Working Place No corrosive gas, inflammable gas, oil mist or dust
Cooling Force-air cooling