Soft Starters - Technical Details
Operation
Operation control mode |
Keyboard/external terminal/RS485 communication |
Start mode |
Current limiting/voltage/heavy load |
Start/stop period |
Digital setting supported |
Start delay |
Digital setting supported |
Emergency stop |
Interrupt output of soft starter |
Limiting current |
Starting current is lower than this value under current limiting and heavy-load mode |
Initial voltage |
Initial voltage supports digital setting under voltage mode |
Light-load control |
Detect accidents such as belt tripping |
Restart |
Support restart in case of shutdown due to a fault |
Fault output |
Contact output - AC 250V 5A, DC 30V 5A |
Multifunction relay output |
Start delay, start, running, stop, complete stop, restart |
Analog output |
0~20mA / 4~20mA, optional |
Protection Function
Soft starter protection |
Overcurrent, overload, overheat, three-phase imbalance, default phase, light load, external fault |
Soft starter alarm |
Emergency shutdown, light load and restart |
Display Keyboard
Running information |
Ready condition, start delay, stating process, operation, stop, fault alarm |
Parameter protection |
Set parameters are protected against modification |
Working Conditions
Category of use |
AC-53b |
|||
Rated insulation voltage |
660V |
Rated impulse withstand voltage |
4kV |
|
Operation frequency |
≤ 12 times/h |
|||
Protection grade |
IP20 |
CDRA011T4~CDRA055T4 |
||
IP00 |
CDRA075T4~CDRA600T4, CDRA-K3G055T4~CDRA-K3G600T4 |
|||
Rated limit short-circuit current |
CDRA055T4: 6kA ; CDRA160T4: 12kA |
|||
CDRA320T4: 20kA; CDRA600T4: 48kA |
||||
CDRA-K3G075T4: 9.1kA ; CDRA-K3G160T4: 12kA |
||||
CDRA-K3G320T4: 20kA; CDRA-K3G600T4: 48kA |
Environment
Ambient temperature |
-10 ℃ ~ 40 ℃ |
Storage temperature |
-20 ℃ ~ 65 ℃ |
Ambient humidity |
Max. 90 % RH. (no condensation) |
Height/vibration |
Below 1,000 m; below 5.9m/s²(=0.6g) |
Application scenario |
No corrosive gas, inflammable gas, oil mist, dust or others |
Cooling Method
Natural air cooling |
CDRA011T4~CDRA600T4, CDRA-K3G055T4~ CDRA-K3G075T4 |
Forced air cooling |
CDRA-K3G093T4~CDRA-K3G600T4 |
Bypass Contactor
In-Built for CDRA-K3 series. Not Available for CDRA series |